Temperature Settings
ADDRESS
NAME
VALUE
UNIT
16384
Room Temperature sp
°C
16388
Air In Max
°C
16390
Air In Differential
K
16392
Air Out Setpoint
°C
16398
Air Out Differential
K
Dp Sensor Settings
ADDRESS
NAME
VALUE
UNIT
16519
dP Sensor Enable
True
False
-
16520
dP Setpoint
Pa
16522
dP Deadband
Pa
16524
dP kpi
%
16526
dP Ti
Sec
16530
dP Range - Min
Pa
16532
dP Range - Max
Pa
Fan Control
NAME
ADDRESS
CONTROL
Fan Minimum Speed (%)
16400
Fan Maximum Speed (%)
16445
Fan Initial Speed (%)
16405
Fan Differential Delay (Sec)
16402
Fan 1
16472
OFF
True
False
Fan 2
16473
OFF
True
False
Fan 3
16474
OFF
True
False
Fan 4
16475
OFF
True
False
Fan 5
16476
OFF
True
False
Fan 6
16477
OFF
True
False
Valve Control
NAME
ADDRESS
VALUE
Valve Minimum Open (%)
16396
Valve Maximum Open (%)
16394
Valve Initial Open (%)
16446
Valve Differential Delay (Sec)
16401
Flow Settings
ADDRESS
NAME
VALUE
UNIT
16813
Flow Sensor Enable
True
False
-
16814
Flow Min Value
L/min
16816
Flow Max Value
L/min
16818
Flow Kpi
-
16819
Flow Ti
Sec
Sleep Mode
ADDRESS
NAME
VALUE
UNIT
16820
Sleep Mode Enable
Enable
Disable
-
16821
Sleep Time
Sec